Quote

Load bank testing

What is a load bank?

A load bank is a device that draws a controlled, measurable electrical load from a power source and turns that energy into heat, so a generator, UPS or other source can be proven at known loads without connecting real equipment to it.

Key facts

How does a load bank work?

A load bank works by passing current through load elements and getting rid of the energy as heat. In the simplest form, as ASCO describes it, precise resistive elements are cooled by an integral fan; the electrical energy in kilowatts leaves the unit as heat. Because the elements are switched in known steps, the load is consistent and repeatable, and it can be controlled, measured and recorded, which is the point: the source under test sees a load you chose, not whatever the building happens to draw that day.

Control ranges from pilot relays, toggles and decade switches to embedded controllers and PC software that capture data, record transients and produce reports with graphs. Larger systems network several load banks under one controller, so a site can apply more load than a single unit could carry.

Power triangle: kW, kVAR and kVAReal power kW on the horizontal side, reactive power kVAR on the vertical side, apparent power kVA on the hypotenuse; the angle between kW and kVA sets the power factor.Real power, kWkVARApparent, kVAPower factor = kW / kVAResistive load: kVAR is zero and kW equals kVA.
A resistive load bank draws kW only; inductive or capacitive load adds kVAR; the source must supply the kVA that combines them.

What types of load bank are there?

There are four types, defined by the kind of load they present: resistive, inductive, capacitive and combined.

TypeLoad it presentsRated inWhat it is used for
ResistiveReal power at unity power factorkWThe most common type; loads an engine, a UPS or a power system to its kW rating
InductiveLagging power factor (current lags voltage)kVARUsed with a resistive unit to reach a source's full kVA rating at a lagging power factor
CapacitiveLeading power factor (current leads voltage)kVARUsed with a resistive unit to simulate leading loads, typical of computer and UPS equipment
CombinedResistive plus reactive elements, switched independentlykVATesting at a chosen power factor from one unit; can include resistive, inductive and capacitive elements (RLC)

The difference matters most for generators and is covered in resistive vs reactive load banks.

What are kW, kVA and kVAR on a load bank?

They are the three sides of the power triangle: kW is real power, kVAR is reactive power and kVA is the apparent power that combines them. A resistive load bank only draws kW, at unity power factor. That fully loads an engine, but ASCO notes that only 80% of a generator set's nameplate kVA can be reached with a resistive unit. Generator sets are usually rated at 0.8 power factor, so proving the alternator at its full kVA takes an inductive element alongside the resistive one.

For a UPS the question is different: what load do you need to prove the power train at its rating? That depends on the UPS and on what the test is meant to show, and it is settled when the test method is written.

What form factors do load banks come in?

Load banks come in six common forms, chosen for where they will be used:

What are load banks used for?

Load banks are used to proof-test power sources: generators first, then UPS systems, switchgear and other parts of a power system. ASCO lists the main uses:

What does a load bank not tell you?

A load bank presents a steady, chosen load, which is its strength and its limit. It tells you how the source behaves at the steps you applied; it does not reproduce every behaviour of a real IT load, and a resistive-only test says nothing about reactive performance. For a UPS it does not prove battery runtime, which needs a capacity test; see UPS and battery load bank testing.

What should be checked before a load bank comes on site?

Four things decide whether a test day goes to plan, and all of them are settled before anyone arrives:

Related pages

Questions

Is a load bank the same as a load bank test?

No. The load bank is the equipment that creates the artificial load; the load bank test is the procedure that uses it to prove a generator, UPS or other source at known load steps.

Does a resistive load bank fully test a generator?

It fully loads the engine, cooling, fuel and exhaust systems to the kW rating, but ASCO notes that only 80% of the nameplate kVA can be reached. A reactive element is needed to test the alternator at its full kVA.

How big a load bank does a test need?

Large enough to reach the rating you want to prove. Load banks can be networked: ASCO's example uses a 3000 kW load bank to test one 1500 kW generator set at full kW, or two in parallel.

Where does the heat go?

Out of the load bank through its fan, so the unit must sit where the heat can be rejected safely, away from sensitive equipment, with cable run from the source under test.

What listings should a load bank carry?

ASCO recommends a third-party listing such as UL 508A, CSA or the CE marking, and design to the applicable IEC, NEMA, NEC and ANSI standards.

Sources, checked 2026-10-04:

Need a UPS serviced, tested or replaced?

Tell us the site, the UPS and the timing. We reply and quote within 4 business hours, or call 1 (438) 800-0382

Request a quote →

Brand names are trademarks of their owners and are used only to identify the equipment we service. We are not the manufacturer and are not affiliated with it.

Call 1 (438) 800-0382Request a quote